+86-371-67851181
+86-371-67849797

Your present location:Home >> About us
  • Details:

    ABC cable
    The product is a new type of aerial cable for power transmitting . It is extensively used in overhead power transmission line. It improves the safety and reliance of electrified wire netting . It is primarily used on lighting, outdoor lighting,and temporary service for construction . To be used at voltage of 600V phase-to-phase or less,and the conductor temperatures no exceed 75℃ for polyethylene insulated conductors 90℃ for crosslinked polyethylene (XLPE) insulated conductors.
    Construction
      Conductors are concentrically stranded,compressed 1350-H19 aluminum. Insulated with either  polyethylene or crosslinked  polyethylene (XLPE). Neutral messengers are concentrically stranded 6201, AAC,or ACSR .

    Duplex service drop (Bare neutral messenger ACSR)

     

    Code 

    word

    AWG or 

    kcmil

    Bare neutral messenger

    Phase conductor 

    Weight 

    kg/km

    ACSR 

    stranding and 

    wires dia. (mm)

    Rated

     strength 

    (lbs)

    AAC

    Insulation 

    thickness

     (mm)

    Stranding 

    and wires 

    dia. (mm)

    Setter

    1*6AWG+

    1*6AWG

    1/1.68+6/1.68

    1190

    1/4.11

    1.14

    111

    Shepherd

    1*6AWG+

    1*6AWG

    1/1.68+6/1.68

    1190

    7/1.56

    1.14

    113

    Eskimo

    1*4AWG+

    1*4AWG

    1/2.12+6/2.12

    1860

    1/5.19

    1.14

    171

    Terrier

    1*4AWG+

    1*4AWG

    1/2.12+6/2.12

    1860

    7/1.96

    1.14

    173

    Chow

    1*2AWG+

    1*2AWG

    1/2.67+6/2.67

    2850

    7/2.47

    1.14

    266

    Bull

    1*1/0AWG+

    1*1/0AWG

    1/3.37+6/3.37

    4380

    19/1.89

    1.52

    427

  • Details:

    ABC cable
    The product is a new type of aerial cable for power transmitting . It is extensively used in overhead power transmission line. It improves the safety and reliance of electrified wire netting . It is primarily used on lighting, outdoor lighting,and temporary service for construction . To be used at voltage of 600V phase-to-phase or less,and the conductor temperatures no exceed 75℃ for polyethylene insulated conductors 90℃ for crosslinked polyethylene (XLPE) insulated conductors.
    Construction
      Conductors are concentrically stranded,compressed 1350-H19 aluminum. Insulated with either  polyethylene or crosslinked  polyethylene (XLPE). Neutral messengers are concentrically stranded 6201, AAC,or ACSR .
     

    Triplex service drop ( bare neutral messenger AAAC )

     

    Code 

    word

    AWG or kcmil

    Bare neutral messenger

    Phase conductor

    Weight

     kg/km

    AAAC 

    stranding 

    and 

    wires dia. (mm)

    Rated 

    strength (lbs)

    AAC

    Insulation 

    thickness (mm)

    Stranding and 

    wires dia. (mm)

    Mines

    2*6AWG+1*30.58

    7/1.68

    1110

    1/4.11

    1.14

    152

    Prawn

    2*4AWG+1*48.69

    7/2.12

    1760

    1/5.19

    1.14

    229

    Shrimp

    2*2AWG+1*77.47

    7/2.67

    2800

    7/2.47

    1.14

    354

    Gammarus

    2*1/0AWG+1*123.3

    7/3.37

    4460

    7/3.12

    1.52

    569

    Dungenese

    2*2/0AWG+1*155.4

    7/3.78

    5390

    7/3.5

    1.52

    702

    Flustra

    2*3/0AWG+195.7

    7/4.25

    6790

    19/2.39

    1.52

    869

  • Details:

    Applications
    To supply power from the utility's lines to the consumer's weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75°C maximum for polyethylene Insulation or 90°C maximum for crosslinked insulation.

    Construction
    Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand 6201 alloy neutral messenger.

    Standards

    ·  B-230 Aluminum Wire 1350-H19 for Electrical Purposes

    ·  B-231 Aluminum Conductors, Concentric-Lay-Stranded

    ·  B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)

    ·  B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors

    ·  B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).

    ·  Triplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA body S-76-474

  • Details:
  • Details:
  • Details:
firstprevious12nextlast