Application
Used for primary and secondary overhead distribution lines where space is limited. Compared with bare conductors, it can prevent short circuits due to the contact with trees or buildings.
1. Conductor: Concentrically stranded AAAC or ACSR or AAC
2. Shield: Semi-conducting cross linked polymer
3. Insulation: XLPE/LDPE
4. Sheath: XLPE/HDPE (optional)
Standard:IEC 60502-2 ICEA S-121-733
Without sheath
Voltage (phase to phase)(V) | Conductor Gauge | Shield thinkness(mm) | Insulation Thickness(mm) | Test voltage kVac |
8001-15000 | 2AWG – 800kcmil | 0.6 | 3.0 | 18 |
15001-25000 | 2AWG – 800kcmil | 0.6 | 4.0 | 30 |
25001-35000 | 1/0AWG – 800kcmil | 0.7 | 7.6 | 42 |
With sheath
Voltage (phase to phase)(V) | Conductor Gauge | Shield thinkness(mm) | Insulation Thickness(mm) | Sheath thickness(mm) | Test voltage kVac |
8001-15000 | 2AWG – 800kcmil | 0.6 | 1.91 | 1.91 | 18 |
15001-25000 | 2AWG – 800kcmil | 0.6 | 3.18 | 1.91 | 30 |
25001-35000 | 1/0AWG – 800kcmil | 0.7 | 4.45 | 3.18 | 42 |
35001-46000 | 1/0AWG – 800kcmil | 0.7 | 5.70 | 4.45 | 50 |