Application
This cable is used in overhead distribution lines of rated voltages 0.6/1KV and below.
Standard
IEC 60502-1: Power cables with extruded insulation and their accessories for rated voltages from 1kV (Um=1.2kV) up to 30 kV (Um=36kV) - Part 1: Cables for rated voltages of 1kV (Um=1.2kV) and 3kV (Um=3.6 kV)
Rated voltage 0.6/1KV & below
Extruded weather-resistant insulation
Max. conductor working temperature 90℃ (XLPE insulation) or 70℃ (PE insulation)
1. 1350 aluminum conductor
2. XLPE Insulation
Size | Conductor Wire No. | Insulation Thickness | Diameter over Insulation | Approx. weight | Min. Breaking Load of Conductor | Max. Conductor DC Resistance @ 20℃ |
mm2 | / | mm | mm | kg/km | kN | Ω/km |
1x16 | 7 | 1.2 | 7.2 | 66 | 2.517 | 1.91 |
1x25 | 7 | 1.2 | 8.4 | 95 | 3.762 | 1.20 |
1x35 | 7 | 1.4 | 9.9 | 131 | 5.177 | 0.868 |
1x50 | 7 | 1.4 | 11.2 | 176 | 7.011 | 0.641 |
1x70 | 19 | 1.4 | 12.8 | 235 | 10.354 | 0.443 |
1x95 | 19 | 1.6 | 14.9 | 322 | 13.727 | 0.320 |
1x120 | 19 | 1.6 | 16.4 | 395 | 17.339 | 0.253 |
1x150 | 19 | 1.8 | 18.4 | 490 | 21.033 | 0.206 |
1x185 | 37 | 2.0 | 20.2 | 610 | 26.732 | 0.164 |
1x240 | 37 | 2.2 | 23.2 | 790 | 34.679 | 0.125 |
1x300 | 37 | 2.4 | 25.6 | 980 | 43.349 | 0.100 |